10-175UL - 1.75 Amp Power Supply (DISCONTINUED - See 10-1 & 10-1FPD)

The 10-175UL is a power-limited power supply that converts 115VAC/60Hz input into two individually PTC-protected* 12V or 24V DC outputs.

The 10-175UL is ideal for access control and applications requiring an interface with Fire Alarm Control Panels. The built-in fire alarm interface input trigger ensures that electromagnetic locking device will be in a fail safe or open position in the event of an alarm.

The 10-175UL must be installed in accordance with national and local electrical codes and regulations.

*Positive Temperature Coefficient - Circuit protection which resets itself automatically.

Applications
Airport Facilties Fire Rated factory inside door Stairwell Exhibit

• To power Access Control Systems
• To power Electric Locking Systems
• Fire Alarm Control Panel Interface
• Health Care Facilities
• Industrial
• Commercial

2 year
STANDARD FEATURES

  • UL listed for access control
  • Fire alarm interface module*
  • Fire alarm reset switch and AC power indicator accessible on front cover
  • Field selectable 12VDC or 24VDC Power Limited output
  • Automatic reset circuit protection
  • 1.75 amp continuous supply current at 12 or 24VDC, field selectable
  • Filtered, electronically regulated output
  • Built-in battery charger (batteries optional)
  • Includes power supply, enclosure, cam lock and transformer

*Life Safety Code requirement

OPTIONS
TD1........... Time Delay option - Delayed Unlock - Manual Relock,  NFPA-101 (15 Sec. Delay)

TD2........... Time Delay option - Delayed Unlock - Auto-Relock
This two stage time delay option provides the same function as the TD1, only, instead of manual relock, the door locks again automatically after the specified (adjustable) period of time.

TD3........... Time Delay option - Instant Unlock - Delayed Auto-Relock
Upon actuation of a momentary switch (e.g. push button, key switch, keypad) the door unlocks immediately and automatically relocks after a preset (adjustable) period of time has elapsed.

TD4........... Time Delay option - 3 Second Nuisance Delay - Manual Relock

TD365........... 365 Day Timer
BB12-4........... 4.5 Ahr Battery (1) 
BB12-7........... 7 Ahr Battery (1)   
BB24-4........... 4.5 Ahr Battery (2)  
BB24-7........... 7 Ahr Battery (2)   
9310RB........... Relay Board

WARRANTY
2 Year Limited Warranty

Housing Dimensions:
15-1/2"H x 12"W x 4-1/2"D
(393.7mm x 304.8mm x 114.3mm)

Power Input:
0.6A @ 115VAC

Current Output:
1.75A @ 12 or 24VDC (switch selectable)

Auxiliary Relay Output:
Form C, 1A @ 28VDC

AC Fail Output Relay:
Form C, 1A @ 28VDC

Charge Current:
Maximum 400mA

Battery Backup:
Varies with battery size (See options section under ORDEING Tab)

NOTE: Model 10-175UL should be installed in accordance with applicable codes.

Certification :

ULUL Listed, CSFM, MEA

Model Description Dimensions Voltage
10-175UL
UL
Filtered, regulated output   
Field selectable voltage, 2 outputs (1 switched; 1 constant),
fire alarm interface module,  battery backup charger, fire alarm reset and AC power indicator located on cover. MEA, CSFM and UL listed.
15-1/2"H x 12"W x 4-1/2"D 12/24VDC-1.75 amps

 

OPTIONS
Model Description Dimensions

TD1 Time Delay option - Delayed Unlock - Manual Relock,  NFPA-101 (15 Sec. Delay) -

TD2 Time Delay option - Delayed Unlock - Auto-Relock
-
TD3 Time Delay option - Instant Unlock - Delayed Auto-Relock
-
TD4 Time Delay option - 3 Second Nuisance Delay - Manual Relock -
TD365 365 Day Timer
-
BB12-4 4.5 Ahr Battery (1)  - 12VDC 
3-1/2"L x 2-3/4"W x 4"H 
BB12-7
7 Ahr Battery (1) - 12VDC
5-15/16"L x 2-9/16"W x 3-1/2"H
BB24-4
4.5 Ahr Battery (2) - 24VDC
3-1/2"L x 2-3/4"W x 4"H
BB24-7 
7 Ahr Battery (2) - 24VDC 5-15/16"L x 2-9/16"W x 3-1/2"H
9310RB
Relay Board - 12/24 VDC-10 amp -